Item | Specifications |
---|
Model | NJ-PA3001 | NJ-PD3001 |
---|
Supply voltage | 100 to 240 VAC (wide-range), 50/60 Hz | 24 VDC |
---|
Operating voltage and frequency ranges | 85 to 264 VAC, 47 to 63 Hz | 19.2 to 28.8 VDC |
---|
Power consumption | 120 VA max. | 60 W max. |
---|
Inrush current *1 | At 100 VAC: 20 A/8 ms max. for cold start at room temperature At 200 VAC: 40 A/8 ms max. for cold start at room temperature | At 24 VDC: 30 A/20 ms max. for cold start |
---|
Output capacity *2 | 5 VDC, 6.0 A (including supply to CPU Unit using CPU Rack) 5 VDC, 6.0 A (using Expansion Rack) 24 VDC, 1.0 A Total: 30 W max. |
---|
Output terminal (service supply) | Not provided |
---|
RUN output *3 | Contact configuration: SPST-NO Switch capacity: 250 VAC, 2 A (resistive load) 120 VAC, 0.5 A (inductive load), 24 VDC, 2A (resistive load) |
---|
Replacement notification function | Not provided |
---|
Insulation resistance *4 | 20 MΩ min. (at 500 VDC) between AC external and GR terminals | 20 MΩ min. (at 500 VDC) between DC external and GR terminals |
---|
Dielectric strength *4 *5 | 2,300 VAC 50/60 Hz for 1 min between AC external and GR terminals Leakage current: 10 mA max. | 1,000 VAC 50/60 Hz for 1 min between DC external and GR terminals Leakage current: 10 mA max. |
---|
Noise immunity | 2 kV on power supply line (Conforms to IEC 61000-4-4.) |
---|
Vibration resistance | 5 to 8.4 Hz, 3.5-mm amplitude, 8.4 to 150 Hz, acceleration: 9.8 m/s2 in X, Y, and Z directions for 100 min (Time coefficient: 10 min × coefficient factor 10 = total time 100 min) (according to IEC 60068-2-6) |
---|
Shock resistance | 147 m/s2 3 times each in X, Y, and Z directions (Relay Output Unit: 100 m/s2) (according to IEC 60068-2-27) |
---|
Ambient operating temperature | 0 to 55°C |
---|
Ambient operating humidity | 10% to 90% (with no condensation) |
---|
Atmosphere | Must be free from corrosive gases. |
---|
Ambient storage temperature | -20 to 75°C |
---|
Grounding | Less than 100 Ω |
---|
Enclosure | Mounted in panel |
---|
Weight | 470 g max. | 490 g max. |
---|
CPU Rack dimensions | 174.7 to 484.7 × 90 × 90 mm (W × D × H) (not including cables) W = 70 (Power Supply Unit) + 90 (CPU Unit) + 20 × n + 31 × m + 14.7 (end cover) n is the number of 32-point I/O Units or I/O Control Units and m is the number of other Units. |
---|
Safety measures | Conforms to cULus, EC Directives, NK, LR, RCM, and KC. |
---|