Technical specifications |
Voltage ranges | PAC3200-1/3: L-N: 3 ... 400 V AC (+ 20 %), max. 347 for UL L-L: 3 ... 690 V AC (+ 20 %), max. 600 for UL min. voltage L-N: 3 ... 40 V AC PAC3200-2: L-N: 3 ... 289 V AC (+ 20 %) L-L: 3 ... 500 V AC (+ 20 %) overvoltage category : CAT III |
Current range | 1 A AC (+ 20 %, max. 300 V) ó 5 A AC (+ 20 %, max. 300 V) (Only for connection to external power transformers) |
Measurement accuracy | Voltage: ± 0.3 % Current ± 0.2 % Power: ± 0.5 % Frequency: ± 0.05 % Power factor: ± 0.5 % Active energy: category 0.5S (IEC 62053-22) Reactive energy: category 2 (IEC 62053-22) In case of measurement through the external current or voltage transformers , the measurement precision depends on the quality of those transformers |
Supply voltage | PAC3200-1/3: 95 … 240 V AC (50 / 60 Hz) ó 110 … 340 V DC PAC3200-2: 22 … 65 V DC overvoltage category : CAT III |
Consumption | 8 VA typical |
Digital inputs | 1 input |
Digital outputs | 1 output |
Connection | PAC3200-1/2: screws PAC3200-3: cable terminal |
Display | monochromatic graphic LCD display resolution: 128 x 96 pixels dimensions: 72 mm x 54 mm update periods: 0,33 ... 3 s, adjustable |
Setting | 4 function keys or software |
Dimensions | 96 x 96 x 51 mm |
Dimensions for panel mounting | 92 x 92 mm |
Temperature range Operating temperature Storage temperature | -10 ... +55 °C -25 ... +70 °C |
Relative humidity | 95 % to 25 °C non condensed |
Protection type | frontal: IP 65 |
Weight | approx. 325 g |
Mounting | mounting clips with screws |