Technical data | EL1809 |
---|
Connection technology | 1-wire |
Specification | EN 61131-2, type 1/3 |
Number of inputs | 16 |
Nominal voltage | 24 V DC (-15 %/+20 %) |
“0” signal voltage | -3…+5 V (EN 61131-2, type 1/3) |
“1” signal voltage | 11…30 V (EN 61131-2, type 3) |
Input current | typ. 3 mA (EN 61131-2, type 3) |
Input filter | typ. 3.0 ms |
Distributed clocks | – |
Current consumption power contacts | typ. 4 mA + load |
Current consumption E-bus | typ. 100 mA |
Electrical isolation | 500 V (E-bus/field potential) |
Bit width in the process image | 16 inputs |
Configuration | no address or configuration setting |
Conductor types | solid wire, stranded wire and ferrule |
Conductor connection | solid wire conductors: direct plug-in technique; stranded wire conductors and ferrules: spring actuation by screwdriver |
Rated cross-section | solid wire: 0.08…1.5 mm²; stranded wire: 0.25…1.5 mm²; ferrule: 0.14…0.75 mm² |
Special features | standard terminal with high number of channels for slow 24 V DC edges, direct plug-in technique |
Weight | approx. 65 g |
Operating/storage temperature | -25…+60 °C/-40…+85 °C |
Relative humidity | 95 %, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos. | IP 20/variable (see documentation) |
Approvals/markings | CE, UL, ATEX |
Ex marking | II 3 G Ex nA IIC T4 Gc |